6 Communication settings and guide of HMI connecting with controller
Modbus TCP Slave Ethernet
Modbus UDP Ethernet
Connection Configuration
Modbus UDP Slave Ethernet
Communication Setting
Modbus RTU RS232 communication:9600, 8, even, 1; station: 1
NOTE: 1. Modbus RTU protocol supports broadcasting station number, but the radio function only
supports write operations, with a reading of properties for the components, can not use the radio function;
2. Radio features are used in two ways: First, write-only properties with components (Bit state setting
device, "switch" method, except); multi-state setting device, "add value", "sub value", "JOG++", "JOG--"
method excluded); Second, the use of macros, the macro programming, on the radio station to write the
address number.
Modbus RTU Extend RS232 communication : 9600, 8, even, 1; station: 1
- 200 -