6 Communication settings and guide of HMI connecting with controller
1007H
1st group of Heating/Cooling
control cycle
0 ~ 99, 0:0.5 sec. in the adjusting mode or
1008H
2nd group of Heating/Cooling
control cycle
0 ~ 99, 0:0.5 sec. in the adjusting mode
1009H PB Proportional band
0.1 ~ 999.9. in the adjusting mode
100AH Ti Integral time
0~9999. in the adjusting mode
100BH Td Derivative time
0~9999. in the adjusting mode
100CH Integration default
0 ~ 100%, unit is 0.1%. in the adjusting mode
100DH
Proportional control offset error
value, when Ti = 0
0 ~ 100%, unit is 0.1%. in the adjusting mode
100EH
The setting of COEF when Dual
Loop output control are used
0.01 ~ 99.99, unit is 0.01 (setting when it is under the
control of PID ) in the adjusting mode
100FH
The setting of Dead band when
Dual Loop output control are used
-999 ~ 9,999. in the adjusting mode
1010H
Hysteresis setting value of the 1st
output group
0~9999. in the adjusting mode or
1011H
Hysteresis setting value of the 1st
output group
0~9999. (setting when Dual Loop output control are
used ) in the adjusting mode or
1012H
Hysteresis setting value of the 1st
output group
Unit is 0.1%; write operation is valid under manual
tuning mode only. In the running mode
1013H
Hysteresis setting value of the 2nd
output group
Unit is 0.1%; write operation is valid under manual
tuning mode only. In the running mode
1014H
Upper-limit regulation of analog
linear output
1 Unit = 2.8uA (Current Output) = 1.3mV (Linear
Voltage Output) in the adjusting mode
1015H
Lower-limit regulation of analog
linear output
1 Unit = 2.8uA (Current Output) = 1.3mV (Linear
Voltage Output) in the adjusting mode
1016H Temperature regulation value
-99.9 ~ +99.9, unit: 0.1. in the adjusting mode
1017H Analog decimal setting
0~3. in the running mode
1018H
Time for valve from full open to
full close
0.1~999.9. in the adjusting mode