6 Communication settings and guide of HMI connecting with controller
Note:Input and Output Modules should match with Master configuration
PLC setting
Note: you can find eview.gsd in the fieldbus file of Kinco HMIware Installation Directory, or you can
download from www.kinco.cn.
1. Setup eview.gsd file
Setup GSD file in the s7-300 software.
Process:
(1). Closed all the station in HW Config
(2).choose “option” > “install GSD file”.
(3).Find out the folder of eview.gsd.
(4).Choose eview.gsd, and then click the install button.
You can find the ico in PROFIBUS DP\MMI, after installing
2. configuration setting
(1)make a new project in s7-300 through the guide
(2)we must use OB82,OB86,OB100,OB121 and OB122 in BLOCK, or system will go wrong when
PLC is power-up.
(3)dblclick HW Config, choose “DP” and right click “add master station”.
- 236 -